§ 5-1016. Additions, insertions, deletions and changes.  


Latest version.
  • (a)

    Section R101.1 Title, insert the words "City of Beaufort." This section shall now read as follows: "These provisions shall be known as the Residential Code for One and Two-Family Dwellings of the City of Beaufort."

    (b)

    Section R108.2 Schedule of Permit Fees, of the International Residential Code for One- and Two-Family Dwellings shall be amended to read as follows: "The fees for residential construction permits and other related services shall be as provided in section 5-1003(f) of the City of Beaufort Code of Ordinances."

    [(c)

    The following table is added:]

    TABLE R301.2(1)
    CLIMATIC AND GEOGRAPHIC DESIGN CRITERIA

    Roof
    Snow
    Load
    Wind Seismic
    Design
    Category f, g
    Subject to Damage From Winter
    Design
    Temp f
    Flood
    Hazards h
    Speed e (mph) Weathering a Frost line
    depth;sup\sup;
    Termite c Decay d
    5LB 130 V 3S /110 fm
    exposure category
    B&C
    D1 Moderate 12" very
    heavy
    moderate
    to severe
    27° April 26,
    1977

     

    For SI: 1 pound per square foot — 0.0479 kN/m.0 , 1 mile per hour = 1.609 km/h.

    a  Weathering may require a higher strength concrete or grade of masonry than necessary to satisfy the structural requirements of this code. The weathering column shall be filled in with the weathering index (i.e., "negligible," "moderate" or "severe") for concrete as determined from the Weathering Probability Map [Figure R301.2(3)]. The grade of masonry units shall be determined from ASTM C34, C55, C62, C73, C90, C129, C145, C216, or C652.

    ;sup\sup; The frost line depth may require deeper footings than indicated in Figure R403.1(1). The jurisdiction shall fill in the frost line depth column with the minimum depth of footing below finish grade.

    c  The jurisdiction shall fill in this part of the table with "very heavy," "moderate to heavy," "slight to moderate," or "none to slight" in accordance with Figure R301.2(6) depending on whether there has been a history of local damage.

    d  The jurisdiction shall fill in this part of the table with "moderate to severe," "slight to moderate," or "none to slight" in accordance with Figure R301.2(7) depending on whether there has been a history of local damage.

    e  The jurisdiction shall fill in this part of the table with the wind speed from the basic wind speed map [Figure R301.2(4)]. Wind exposure category shall be determined on a site-specific basis in accordance with Section R301.2.1.4.

    f  The outdoor design dry-bulb temperature shall be selected from the columns of 97½-percent values for winter from Appendix D of the International Plumbing Code. Deviations from the Appendix D temperature shall be permitted to reflect local climates or local weather experience as determined by the building official.

    g  The jurisdiction shall fill in this part of the table with (a) the date of the jurisdiction's entry into the National Flood Insurance Program (date of adoption of the first code or ordinance for management of flood hazard areas), (b) the date(s) of the currently effective FIRM and FBFM, or other flood hazard map adopted by the community, as may be amended.

(Ord. No. O-24-02, 6-25-02; Ord. No. O-02-10, § 2, 1-26-10)